|
Power Glossary
November, 2003
Are you confused about all of the
terms and acronyms used by power contractors and vendors?
This simplified glossary may help. (Also
see Backup Power Systems)
AC:
Alternating Current.
Alternating
Current (AC): Current that alternates from positive to negative.
AC is the normal current used to power most devices in homes and
businesses. (Compare to Direct
Current.)
Ampere
(amp): A measurement of current flow, often abbreviated as amps.
Arrester:
A device to suppress voltage spikes, sometimes called suppressor or protector.
(See Suppressor.)
Battery:
An electrical storage device that produces direct current.
Blackout:
A loss of alternating current (AC).
Brownout:
A low voltage situation. Some
equipment will not work in a brownout, whereas others will, depending on the
severity. In either case, a brownout
is bad for electrical equipment. (See
Undervoltage.)
Circuit
Breaker: A resettable device that interrupts current flow when it exceeds a
preset level, thereby preventing damage to circuit elements.
(Compare to Fuse.)
Current:
The flow of electricity in a circuit; it is measured in amperes (which is often
shortened to amps).
DC:
Direct Current.
Dip:
A short brownout, often caused by motors turning on and off, such as on large
air conditioners.
Direct
Current (DC): Electricity where current flows in one direction, such as from
a battery. (Compare to Alternating
Current.)
Dropout
Voltage: The voltage at which a device fails to operate properly or safely.
Computer systems will reboot, reset, or lose data when line voltage falls
below approximately 95-100 Volts AC. (See
Brownout and Undervoltage.)
Efficiency:
The ratio of output energy to input energy.
For uninterruptible power supplies (UPSs), it is the amount of energy
lost in the form of heat during DC to AC inverter operation.
Filter:
An electronic device that blocks certain frequencies while allowing other
frequencies, such as 60 hertz (Hz), to pass.
Frequency:
The number of cycles of current flow in one second.
In North America, the frequency of commercial and residential service is
60 cycles per second or 60 Hz.
Fuse:
A device that breaks, thereby opening the circuit and protecting the equipment
connected to it, when the current passing through it exceeds its rated value.
A fuse can be used only once, whereas a circuit breaker, which
accomplishes the same thing, can be reused. (Compare to Circuit Breaker.)
Generator:
A gasoline, natural gas, or propane powered engine that produces electricity.
Generators are often used with uninterruptible power supply (UPS)
systems. Since generators require a
few minutes to stabilize after being started, UPSs are often used for short
duration outages and generators reserved for longer power interruptions.
Some less sophisticated generators may have a problem with frequency
regulation, never appearing to the UPS as a stable power source.
Ground:
A connection, either intentional or inadvertent, between an electrical circuit
and the earth.
Hertz
(Hz): A measure of the frequency of alternating cycles in an AC current per
second. (See Frequency.)
Hot
Swappable Battery: A feature that
allows an uninterruptible power supply (UPS) battery to be changed for
maintenance without taking the UPS and the equipment connected to it, off-line.
Hz:
Abbreviation for hertz. (See
Frequency.)
Inverter:
A device that converts DC power to AC power.
Isolation
Transformer: A transformer inserted to reduce noise and isolate a circuit.
These are used in many larger uninterruptible power supply (UPS) systems.
kVA:
An acronym for kilovolt-amps (See VA) that is a measure of apparent power; 1 kVA
= 1000 VA.
kW:
An acronym for kiloWatt (See Watt) that is a measure of real power; 1 kW = 1000
Watts.
Line
Conditioner: A device that optimizes the quality of commercial power.
By definition, an uninterruptible power supply (UPS) system is a line
conditioner, but a line conditioner isn't always a UPS.
Load:
The electrical devices that use power.
Outage:
A long-term loss of power.
Overvoltage:
By definition, a voltage that is at least 10% above normal.
(See Spike and Surge.)
Peak
Voltage: Also called peak-to-peak voltage, it is a measure of an AC waveform
of the highest peak-to-peak voltage present on the waveform.
A proper 120V AC waveform will have a peak voltage of about 170 volts.
(Compare to RMS voltage.)
Response
Time: The time it takes for a UPS, conditioner, suppressor, fuse, or circuit
breaker to sense and react to a surge or spike.
RMS:
Acronym for Root-Mean-Square, a formula used to calculate effective voltage.
The RMS value of normal AC power is 120V.
(Compare to Peak Voltage.)
Rolling
Blackouts/Rolling Brownouts: A condition where power utilities purposely
impose blackouts or brownouts over a portion of their service area to free up
capacity so that the remaining service area can continue to be served.
After a time, another portion of the service area has a blackout or
brownout imposed on it, so that power can be restored in the original area.
Sag:
See Undervoltage.
Sine
Wave: The shape of an ideal AC waveform.
Most high-end uninterruptible power supplies (UPSs) provide an accurate
sine wave. Some less sophistical
UPSs produce a square wave, which may cause some devices to not work properly or
to shorten their life span.
Spike:
A high voltage condition which lasts for a short duration, usually less than 1
millisecond. A spike can be
thousands of volts. (See Overvoltage
and Surge.)
Square
Wave: It is an undesirable waveform for critical computing applications, as
it is harder on equipment and may cause undesired side effects.
(Compare to Sine Wave.)
Standby
UPS: An uninterruptible power supply (UPS) that passes line power straight
through to the output when conditions are stable, but switches to battery power
when line voltage drops
Suppressor:
A device that diverts voltage surges to an electrical ground.
(See Arrester.)
Surge:
A voltage increase lasting for several cycles or more.
(See Overvoltage and Spike.)
Transfer
Time: The time it takes to switch from AC line power to battery power.
Transformer:
A device used for changing AC voltage or isolating a circuit from its power
source.
Undervoltage:
By definition, it is voltage at 90% or less of the normal level for more than
one minute. Sometimes it is called a
brownout.
UPS
(Uninterruptible Power Supply): A device that provides continuous, acceptable
("clean") power to its load, regardless if the commercial utility's power is
present or of proper quality.
VA:
See volt-amp.
Volt:
A unit of measure for voltage, which is electrical pressure that forces current
to flow.
Volt-amp:
A unit of measurement of apparent power. Most
UPS systems are rated in volt-amps; the actual wattage is about 60-70% of the
VAs.
Watt:
A measurement of true power consumption. Watts
= VA divided by Power Factor.
Return
to List of Articles || Read more articles at MyArticleArchive.com
|